2YSL(St)CY-J 0.6/1 kV EMV

Download PDF

Add to inquiry

Download PDF

To inquiry

PE/PVC motor power supply cable, screened

Control and electronics cables

Double screened 2YSL(St)CY-J cables were designed as supply and connecting cables, for medium mechanical stress, fixed installation and occasionally non-guided movements, in dry, damp and wet rooms. UV-resistant black sheath is designed for outdoor applications. Double screening considerably improves electromagnetic compatibility (EMC) in buildings and plants.

Design

This product consists of:

  • 1
    Kupferleiter, feindrähtig
  • 2
    Aderisolation (PE), Adern mit optimaler Schlaglänge verseilt
  • 3
    Bebänderung (Kunststofffolie, optional)
  • 4
    Schirm (kunststoffkaschierte Aluminiumfolie und Geflechtschirm aus verzinnten Kupferdrähten)
  • 5
    Mantel (PVC, transparent (2YSL(St)CY-J) oder schwarz (2YSL(St)CYK-J))

Technical Data

Standard: DIN VDE 0276-603
Test Voltage: 4 kV / 50 Hz
Rated Voltage: 0.6/1 kV (Uo/U)
Bending radius (min.): 15 x Ø of cable (free motion)
Fire properties: EN 60332-1-2: self-extinguishing and flame retardant
Core identification: HD 308 S2
Temperature range: 
  • Laying temperature: min. 5°C
  • Conductor temperature: max. 70°C
  • Short circuit temperature: max. 160°C
  • Fixed installation: -30°C up to 80°C
  • Flexible use: -5°C up to 70°C
Cable image - 2YSL(St)CY-J 0.6/1 kV EMV
+
-
Cable image - 2YSL(St)CY-J 0.6/1 kV EMV
+
-
Cable image - 2YSL(St)CY-J 0.6/1 kV EMV
+
-

Contact us

Are you interested in this product?

Dogan Özcan, MSc

Product supervisor

+43 (0) 1 70170-154
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section (mm²)
Max. conductor resistance (Ω/km)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
Standard lengths/packing (m)
4 G 1,5
13.3
10.6
244
500 T, 1000 T
4 G 2,5
7.98
12.3
318
500 T, 1000 T
4 G 4
4.95
14.0
515
500 T, 1000 T
4 G 6
3.3
16.1
670
500 T, 1000 T
4 G 10
1.91
19.7
914
500 T, 1000 T
4 G 16
1.21
23.0
1367
500 T, 1000 T
4 G 25
0.78
27.3
1970
500 T, 1000 T
4 G 35
0.554
30.3
2763
500 T, 1000 T
4 G 50
0.386
35.0
3126
500 T, 1000 T
4 G 70
0.272
40.0
4182
500 T, 1000 T
4 G 95
0.206
45.0
5725
500 T, 1000 T
4 G 120
0.161
51.9
6504
500 T
4 G 150
0.129
57.5
7043
300 T
4 G 185
0.106
61.1
8384
300 T
4 G 240
0.801
70.0
12500
300 T

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Control and electronics cables

Browse products
Control and electronics cables
Control and Electronic Cables
Conductors
Fire Alarm Cables
Halogen-free Cables and Wires
Halogen-free Control and Electronic Cables
Halogen-free Power Cables
Halogen-free Telecommunication Cables
Industrial Cables
Railway Signalling Cables
Solar Cables
Telecommunication Cables
PVC and Rubber Cables and Wires
Power Cables and Overhead Lines 0.6/1 kV
Safety Cables
Telecommunications cables
Medium Voltage Cables 10 - 30 kV
Silicone, PUR and Building Site Cables

Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.

Let's work
together

SKW

SKB Group

SKW

SKW Schwechater Kabelwerke GmbH

Himberger Straße 50, 2320 Schwechat

  • +43 1 70170 0

  • [email protected]

Follow us:

  • Terms and Conditions

  • Impressum

  • Compliance

  • Privacy Policy

  • Whistleblowing

All rights reserved. Copyright © 2026