XLPE/HDPE medium voltage underground cable, longitudinally water-proof

Copper - VDE

For fixed installation for high requirements in the ground subject to external effects of moisture, in the open air and in cable ducts for industrial and distribution mains – as permitted by the local building regulations – under severe mechanical stressing during installation and operation.

Design

This product consists of:

  • 1
    Kupferleiter, rund mehrdrähtig verdichtet (RM)
  • 2
    Innere Leitschicht (leitfähiges XLPE)
  • 3
    Aderisolation (XLPE)
  • 4
    Äußere Leitschicht (leitfähiges XLPE) und eine Bebänderung mit einem leitfähigen Band
  • 5
    Schirm (blanke Kupferdrähte und Querleitwendel)
  • 6
    Quellvlies unter und über der Schirmung
  • 7
    Mantel (HDPE schwarz, UV-beständig, mind. Härte 55 ShD)

Technical Data

Standard: DIN VDE 0276-620
Certificate: VDE Germany
Test Voltage: 18 kV
Rated Voltage: 6/10 kV (Uo/U)
Bending radius (min.): 15 x Ø of cable
Fire properties: CPR-Klassifizierung: Fca
Temperature range: 
  • Laying temperature: min. -20°C
  • Operating temperature: -20°C up to 80°C
  • Conductor temperature: max. 90°C
  • Short circuit temperature: max. 250°C
Cable image - N2XS(F)2Y 6/10 kV
+
-
Cable image - N2XS(F)2Y 6/10 kV
+
-
Cable image - N2XS(F)2Y 6/10 kV
+
-

Contact us

Are you interested in this product?

Dogan Özcan

Product supervisor

+43 (0) 1 70170-154
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section / cross-section of screen (mm²)
Number of cores x nominal cross-section / cross-section of screen (mm²)
Mutual capacitance (nF/km)
Max. conductor resistance (Ω/km)
Current rating in the earth (A)
Current rating in the air (A)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
Standard lengths/packing (m)
1 x 35 RM / 16
0.24
0.524
187
197
26.0
915
500 T, 1000 T
1 x 50 RM / 16
0.26
0.387
220
236
27.0
1120
500 T, 1000 T
1 x 70 RM / 16
0.3
0.268
268
294
28.0
1330
500 T, 1000 T
1 x 95 RM / 16
0.31
0.193
320
358
30.0
1620
500 T, 1000 T
1 x 120 RM / 16
0.34
0.153
363
413
32.0
1870
500 T, 1000 T
1 x 150 RM / 25
0.39
0.124
405
468
33.0
2260
500 T, 1000 T
1 x 185 RM / 25
0.42
0.099
456
535
35.0
2630
500 T, 1000 T
1 x 240 RM / 25
0.47
0.075
526
631
38.0
3220
500 T, 1000 T
1 x 300 RM / 25
0.51
0.060
591
722
40.0
3810
500 T, 1000 T
1 x 400 RM / 35
0.57
0.047
662
827
43.0
4850
500 T, 1000 T
1 x 500 RM / 35
0.63
0.037
744
949
46.0
5800
500 T, 1000 T

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Earthing and Short Circuiting Cables and Bare Wires

Browse products
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Safety Cables with circuit integrity
Medium Voltage Cables up to 36 kV
Rubber, Silicone and PUR Cables
Commercial Vehicles and EVC Cables
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables
Special Cables

Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.

Let's work
together

SKW

SKB Group

SKW logo

SKW Schwechater Kabelwerke GmbH

Himberger Straße 50, 2320 Schwechat

  • +43 1 70170 0

  • [email protected]

  • Terms and Conditions

  • Impressum

  • Compliance

  • Privacy Policy

  • Whistleblowing

All rights reserved. Copyright © 2025