NA2XS(F)2Yv 12/20 kV

Download PDF

Add to inquiry

Download PDF

To inquiry

XLPE/HDPE medium voltage underground cable, longitudinally water-proof

Medium Voltage Cables 10 - 30 kV

For fixed installation for high requirements in the ground subject to external effects of moisture, in the open air and in cable ducts for industrial and distribution mains – as permitted by the local building regulations – under severe mechanical stressing during installation and operation.

Design

This product consists of:

  • 1
    Aluminiumleiter, rund mehrdrähtig verdichtet (RM)
  • 2
    Innere Leitschicht (leitfähiges XLPE)
  • 3
    Aderisolation (XLPE)
  • 4
    Äußere Leitschicht (leitfähiges XLPE)
  • 5
    Bebänderung mit einem leitfähigen Band
  • 6
    Schirm (blanke Kupferdrähte und Querleitwendel)
  • 7
    Quellvlies über der Schirmung
  • 8
    Mantel (HDPE schwarz, UV-beständig)

Technical Data

Standard: DIN VDE 0276-620
Certificate: VDE Germany
Test Voltage: 36 kV
Rated Voltage: 12/20 kV (Uo/U)
Bending radius (min.): 15 x Ø of cable
Temperature range: 
  • Laying temperature: min. -20°C
  • Operating temperature: -50°C up to 90°C
  • Conductor temperature: max. 90°C
  • Short circuit temperature: max. 250°C
Cable image - NA2XS(F)2Yv 12/20 kV
+
-
Cable image - NA2XS(F)2Yv 12/20 kV
+
-
Cable image - NA2XS(F)2Yv 12/20 kV
+
-

Contact us

Are you interested in this product?

Dogan Özcan, MSc

Product supervisor

+43 (0) 1 70170-154
[email protected]

Options

Add to inquiry
Number of cores x nominal cross-section / cross-section of screen (mm²)
Number of cores x nominal cross-section / cross-section of screen (mm²)
Mutual capacitance (nF/km)
Max. conductor resistance (Ω/km)
Current rating in the earth (A)
Current rating in the air (A)
Outer diameter appr. (mm)
Total weight appr. (kg/km)
1 x 35 RM / 16
0.16
0.868
146
155
28.0
650
1 x 50 RM / 16
0.18
0.641
172
185
28.9
780
1 x 70 RM / 16
0.2
0.443
210
231
30.8
890
1 x 95 RM / 16
0.22
0.32
251
280
32.5
1000
1 x 120 RM / 16
0.24
0.253
325
289
33.9
1100
1 x 150 RM / 25
0.26
0.206
319
366
35.1
1290
1 x 185 RM / 25
0.27
0.164
361
420
36.9
1440
1 x 240 RM / 25
0.31
0.125
417
4696
39.2
1660
1 x 300 RM / 25
0.33
0.1
471
569
41.7
1900
1 x 400 RM / 35
0.37
0.078
535
660
45.2
2350
1 x 500 RM / 35
0.41
0.061
602
767
48.5
2750
1 x 630 RM / 35
0.43
0.047
675
890
52.0
3240
1 x 800 RM / 35
0.48
0.037
750
1015
56.2
3880
1 x 1000 RM / 35
0.54
0.029
820
1135
60.9
4570

Technical changes reserved.

All figures are therefore without guarantee.

To inquiry

Check other recommended products by SKB Group

Medium Voltage Cables 10 - 30 kV

Browse products
Medium Voltage Cables 10 - 30 kV
Control and Electronic Cables
Conductors
Fire Alarm Cables
Halogen-free Cables and Wires
Halogen-free Control and Electronic Cables
Halogen-free Power Cables
Halogen-free Telecommunication Cables
Industrial Cables
Railway Signalling Cables
Solar Cables
Telecommunication Cables
PVC and Rubber Cables and Wires
Control and electronics cables
Power Cables and Overhead Lines 0.6/1 kV
Safety Cables
Telecommunications cables
Silicone, PUR and Building Site Cables

Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.

Let's work
together

SKW

SKB Group

SKW

SKW Schwechater Kabelwerke GmbH

Himberger Straße 50, 2320 Schwechat

  • +43 1 70170 0

  • [email protected]

Follow us:

  • Terms and Conditions

  • Impressum

  • Compliance

  • Privacy Policy

  • Whistleblowing

All rights reserved. Copyright © 2026